Front of card
Back of card
Furnish New Battery Enersys PowerSafe FTC 23P 0 25
Technology: Pb_Ca_VLA_Flooded.pngFurnish New Battery Enersys PowerSafe FTC 23P 0 25
$1,592.14
Build my Battery
Recycle My Battery
Furnish New Battery Enersys PowerSafe FTC 23P 0 25
| Battery Model | Enersys PowerSafe FTC 23P 0 25 |
|---|---|
| Adjustment | 1 |
| AH Per String | 1800 |
| AH Per String Rating | 8 hr @ 1.75 VPC |
| Cells Per Unit | 1 |
| Nominal VPC | 2 |
| Model KWH | 4 |
| Charge VPC | 2.4 (Min: 2.37, Max: 2.4) |
| Discharge VPC | Min: 1.6, Max: 1.9 |
| Operational Temp Comp | -0.003 V/°C/cell |
| Cycle Temp Comp | -0.004 V/°C/cell |
| Discharge Temp Range | -17.778°C to 40°C |
| Charge Temp Range | -17.778°C to 40°C |
| ISC Amps | 12155 |
| Internal Resistance | 0.0011 Ohms |
| Dimensions (L x W x H) | 11.1 x 14.5 x 22.7 in |
| Weight | 319.2 lbs |
| Number of Posts | 2 |
| Terminal Bolt Diameter | 0.25 in (0_25 mm) |
| Torque (Initial / Maintenance) | 110 / 115 in-lbs |
| Container | V0 |
| Terminal | 0_25 |
| FOB | T |
| Max Continuous Discharge | 5400 Amps |
| Max Charge Amps | 540 Amps |
| Max In Series / Parallel | 0 / 0 |
| Watts Per Cell (15min 1.67) | 2021 |
| Watts Per Cell Rating | 15 min @ 1.67 VPC |
| Weight of Electrolyte | 79.40008822 lbs |